Verifying The Hydran 201 Sensor And Its Parameters; Verifying And Setting The Battery Alarm Parameters - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

2.
Verify and set, as required, all parameters except Period B.
6.4.6

Verifying the Hydran 201 Sensor and Its Parameters

For details on the parameters and commands in the submenu Service, see Section 4.5.4 on
page 4-18.
1.
Access the submenu H201Ti V2.2x;Service.
2.
Access the submenu Service;SensorCal Data.
3.
Ensure the displayed serial number, the ten parameters (B, M, N, S and A1 to A6) and
the checksum all correspond to the values on the Test Certificate and Data Sheet (for
an example, see Figure 6-1 on page 6-4).
4.
Access the command Force Sensor Test.
5.
Push ENTER. The message AreYou Sure?;PressEnter.. is now displayed.
6.
Push ENTER again to confirm.
7.
When asked to enter the password #1 (1253), use the UP and ENTER keys.
8.
The message Please wait... appears, the test is executed (during a four-second
countdown), and the Hydran 201Ti's display should indicate the message Good. If
another message is displayed, see Section 12.1.3 on page 12-2.
Note: The keypad cannot be used for two minutes following a sensor test. Wait before
resuming the configuration.
6.4.7

Verifying and Setting the Battery Alarm Parameters

1.
Access the submenu H201Ti V2.2x;Service.
2.
Access the submenu Service;Battery.
3.
Verify the battery voltage (Battery). For details, see Section 6.1.4 on page 6-5.
4.
Verify and set, as required, the three alarm parameters.
Part 17997
Rev. 6, March 2011
Configuring the Hydran 201Ti
6-33

Advertisement

Table of Contents
loading