Chapter 6 • Hydran 201Ti Installation
6.3.7

Fastening the Hydran 201Ti to the Brass Adaptor

1.
Using the supplied 3/16-in Allen key, fasten the H201Ti's heating plate to the brass
adaptor with the six 1/4-28 cap screws. See Figure 6-8 on page 6-25.
Be careful not to squeeze the nearby electrical wires between the
WARNING
CAUTION
lockwashers and the heating plate or not to damage the supervisory
link (and analog output) termination board.
Note: When the H201Ti is installed horizontally, the terminals must be facing up and
located under the sensor. Also, ensure the bleed screw and sampling port remain easy to
access.
2.
Plug the twist-lock female connector of the sensor cable to the male connector behind
the Hydran 201 sensor.
6-24

Figure 6-7 - Purging Air From the Hydran 201 Sensor

Rev. 6, March 2011
Part 17997