Chapter 6 • Hydran 201Ti Installation
6.4

CONFIGURING THE HYDRAN 201TI

The H201Ti can be configured using either its keypad or a host computer running the
Hydran Host software. It is recommended to use the Hydran Host software because the
configuration task is much easier. For details, see the Hydran Host Software Manual.
The H201Ti's user interface is described thoroughly in Section 4.1 on page 4-1. The
parameter verification detailed in the following pages is written for those who are using the
H201Ti's keypad.
Note: The values indicated in this Section are only given as an indication and may differ
from customer requirements. The value of the various parameters should be decided during
the planning stage of the installation. Ensure to verify all parameters.
6.4.1

Setting the Communication Parameters for the Hydran Host Software

Proceed as follows in order to use a host computer:
1.
Connect the supplied RS-232 cable to the Hydran 201Ti's DB-9 male RS-232
connector (see item 5 in Figure 2-2 on page 2-5), located at the back of the CPU
module.
2.
Using the H201Ti's keypad, access the submenu H201Ti V2.2x;Communication.
3.
Press ENTER to access the parameter CommChannel (communication channel).
4.
Set the parameter CommChannel to H201Ti-DB-9.
5.
Press ENTER to confirm the modification.
6.
Press END.
Note: Do not change the parameter DefaultChannel. The H201Ti returns automatically to
the default channel if there is no communication during five minutes.