Appendix A • Technical Specifications for the Hydran 201i System
A.2
HYDRAN 201CI-C COMMUNICATIONS CONTROLLER
GENERAL
Description Remote controller for one to four Hydran 201Ti's; manages communi-
Components Electronic unit housed in a waterproof enclosure, suitable for outdoor
Application Supervision of one to four H201Ti's and/or a network of up to
ELECTRONIC UNIT
Functions Management of communications transmitted from:
Display None
Analog Outputs None
Alarm Contacts None
COMMUNICATIONS/NETWORKING
Supervisory Link • Connects with one H201Ti
RS-485 Local Network
Link (Isolated)
RS-232 or USB Link • Standard RS-232 port (DB-9 connector), or standard USB link
Recommendation Run all communication cables in flexible or rigid, metallic conduits for
A-4
cations, including networking
installation
128 H201Ti's via a single RS-232 or USB port, either locally or
remotely through an optional modem
• H201Ti's (supervisory link)
• H201Ci Controllers (H201Ci-C's and/or H201Ci-1's) in the network
(RS-485 link)
• A host computer (RS-232 or USB link)
• 2,000-V RMS isolated
• A 2-twisted-pairs (16 or 18 AWG) cable with overall shield is
required per H201Ti
• Maximal length (all cables added up): 1,200 m (4,000 ft)
• Power supply: Separate, isolated, impedance-protected, +15 Vdc
• Standard RS-485 communication port allows daisy-chaining of up
to 32 H201Ci Controllers (H201Ci-C's and/or H201Ci-1's) via the
Main Terminal Block
• One twisted triad (16 or 18 AWG) with overall shield required
• Maximal total daisy-chain length: 1,200 m (4,000 ft)
(type-B connector)
• Allows serial communications with a local host computer (or
remotely with optional modem)
• Any H201Ti can be accessed through any H201Ci Controller in the
local network
maximum mechanical and electrical protection
Rev. 6, March 2011
Part 17997