Appendix A • Technical Specifications for the Hydran 201i System
A.2

HYDRAN 201CI-C COMMUNICATIONS CONTROLLER

GENERAL
Description Remote controller for one to four Hydran 201Ti's; manages communi-
Components Electronic unit housed in a waterproof enclosure, suitable for outdoor
Application Supervision of one to four H201Ti's and/or a network of up to
ELECTRONIC UNIT
Functions Management of communications transmitted from:
Display None
Analog Outputs None
Alarm Contacts None
COMMUNICATIONS/NETWORKING
Supervisory Link • Connects with one H201Ti
RS-485 Local Network
Link (Isolated)
RS-232 or USB Link • Standard RS-232 port (DB-9 connector), or standard USB link
Recommendation Run all communication cables in flexible or rigid, metallic conduits for
A-4
cations, including networking
installation
128 H201Ti's via a single RS-232 or USB port, either locally or
remotely through an optional modem
• H201Ti's (supervisory link)
• H201Ci Controllers (H201Ci-C's and/or H201Ci-1's) in the network
(RS-485 link)
• A host computer (RS-232 or USB link)
• 2,000-V RMS isolated
• A 2-twisted-pairs (16 or 18 AWG) cable with overall shield is
required per H201Ti
• Maximal length (all cables added up): 1,200 m (4,000 ft)
• Power supply: Separate, isolated, impedance-protected, +15 Vdc
• Standard RS-485 communication port allows daisy-chaining of up
to 32 H201Ci Controllers (H201Ci-C's and/or H201Ci-1's) via the
Main Terminal Block
• One twisted triad (16 or 18 AWG) with overall shield required
• Maximal total daisy-chain length: 1,200 m (4,000 ft)
(type-B connector)
• Allows serial communications with a local host computer (or
remotely with optional modem)
• Any H201Ti can be accessed through any H201Ci Controller in the
local network
maximum mechanical and electrical protection
Rev. 6, March 2011
Part 17997

Advertisement

Table of Contents
loading

Table of Contents