• A supervisory link cable connected to a H201Ci-C requires two twisted pairs and an
overall shield.
• If, for special considerations, the H201Ti's analog output is used, select a cable with
characteristics similar to the supervisory link cable but with an additional pair of wires.
The procedure is as follows:
1.
Run the supervisory link cable into the conduit up to the H201Ci Controller, where it
will be connected later.
2.
Ensure all wires are identified.
3.
Connect the cable wires and shield to the H201Ti's supervisory link (and analog
output) termination board. For wiring details, see Table D-6 on page D-3.
The H201Ti's operation may be affected if wires are not connected
WARNING
CAUTION
correctly. Be careful when installing and inserting each wire. Be sure
to insert all strands in the terminal; strands that touch two terminals
cause problems. Strip each wire to a maximum of 8 mm before
installing it. Do not leave trims of metallic strands inside the
H201Ti's enclosure.
4.
Connect the analog output wires to the SCADA system.

6.3.10 Installing the Alarms Cable (Facultative)

If the Hydran 201Ti's alarms are used, proceed as follows:
1.
Run the alarms cable through the second conduit up to the H201Ti.
2.
Connect the cable to the H201Ti's Alarm Contacts 9-Terminal Block (item 12 in
Figure 2-5 on page 2-9). For wiring details, see Table D-2 on page D-1.
3.
Connect the cable to the SCADA system.

6.3.11 Installing the ac Power Supply Cable

1.
Run the three-wire ac power supply cable into the second conduit up to the
Hydran 201Ti.
Part 17997
Rev. 6, March 2011
Installation
6-27