The H201Ti is verified as follows:
1.
Check for oil leaks.
2.
If necessary, clean and retighten the brass adaptor and the H201 sensor.
3.
Check for loose connections on the terminal blocks and connectors. Retighten if
necessary.
WARNING
ac power supply voltage is present on most terminals.
CAUTION
4.
Verify the LED's, the heater, the display and the keypad by performing the procedure
in Section 6.2.2 on page 6-7.
5.
Using the H201Ti's keypad or a host computer running the Hydran Host software
(see the Hydran Host Software Manual), verify the date and time in the Date&Time
submenu (Section 4.5.5 on page 4-21) by performing the procedure in Section 6.4.9
on page 6-34. If they must be adjusted, see Section 6.2.3 on page 6-8.
6.
Verify the four parameters in the History;HistoSetup submenu (Section 4.5.1.5 on
page 4-15). If they must be adjusted, see Section 6.4.2 on page 6-31.
7.
Verify the parameters in the Gas submenu (Section 4.5.2 on page 4-16). If they must
be adjusted, see Section 6.4.3 on page 6-31.
8.
Verify the parameters in the Temperature submenu (Section 4.5.3 on page 4-17). If
they must be adjusted, see Section 6.4.5 on page 6-32.
9.
Verify the Period A and Period B parameters in the Temperature;DynOil Sampl
submenu.
10. Verify the SerialNumber, the ten H201 sensor parameters and the CheckSum (all in
the Service;SensorCal Data submenu, Section 4.5.4.1 on page 4-18) correspond to
those written on the Test Certificate and Data Sheet (see an example in Figure 6-1 on
page 6-4). If those parameters must be adjusted, see Section 6.4.6 on page 6-33.
Part 17997
Rev. 6, March 2011
Hydran 201Ti Verification
13-5