Chapter 12 • Troubleshooting
• Sensor Not Inst!: See Section 12.1.19 on page 12-11.
• SensTemp H: See Section 12.1.20 on page 12-12.
• SensTemp HH: See Section 12.1.21 on page 12-12.
• SensTemp L: See Section 12.1.22 on page 12-13.
• SensTemp LL: See Section 12.1.23 on page 12-13.
• Setup Lost: See Section 12.1.24 on page 12-13.
12.1.1

Battery L

• Alarm type: Fail alarm
• Non-abbreviated description: Battery voltage Low
• Priority: Very low
• Parameter(s) involved:
– Batt. L; SysOK Relay;FaultTrig. submenu; Section 4.5.7 on page 4-23
– Batt.Alr L (alarm set point); Service;VoltPile submenu; Section 4.5.4.3 on page 4-20
– BattAlr Delay; Service;VoltPile submenu; Section 4.5.4.3 on page 4-20
• Alarm cause(s): Battery voltage below the Batt.Alr L alarm set point
Replace the battery within the next nine months. For details, see Section 2.7.1 on
page 2-15.
12.1.2

Battery LL

• Alarm type: Fail alarm
• Non-abbreviated description: Battery voltage Low-Low
• Priority: Low
• Parameter(s) involved:
– Batt. LL; SysOK Relay;FaultTrig. submenu; Section 4.5.7 on page 4-23
– Batt.Alr LL (alarm set point); Service;VoltPile submenu; Section 4.5.4.3 on
page 4-20
– BattAlr Delay; Service;VoltPile submenu; Section 4.5.4.3 on page 4-20
• Alarm cause(s): Battery voltage below the Batt.Alr LL alarm set point
Replace the battery within the next three months. For details, see Section 2.7.1 on
page 2-15.