12.1.22 Senstemp L; 12.1.23 Senstemp Ll; 12.1.24 Setup Lost - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

12.1.22 SensTemp L

• Alarm type: Fail alarm
• Non-abbreviated description: Sensor temperature Low
• Priority: Low
• Parameter(s) involved:
– SensTemp L; SysOK Relay;FaultTrig. submenu; Section 4.5.7 on page 4-23
– STempAlr L (alarm set point); Temperature submenu; Section 4.5.3 on page 4-17
– TempoAlr Delay; Temperature submenu; Section 4.5.3 on page 4-17
• Alarm cause(s): Temperature of the Hydran 201 sensor below the STempAlr L alarm
set point
Although the H201 sensor is not affected by the temperature, monitor its temperature
regularly.

12.1.23 SensTemp LL

• Alarm type: Fail alarm
• Non-abbreviated description: Sensor temperature Low-Low
• Priority: Medium
• Parameter(s) involved:
– SensTemp LL; SysOK Relay;FaultTrig. submenu; Section 4.5.7 on page 4-23
– STempAlr LL (alarm set point); Temperature submenu; Section 4.5.3 on page 4-17
– TempoAlr Delay; Temperature submenu; Section 4.5.3 on page 4-17
• Alarm cause(s): Temperature of the Hydran 201 sensor below the STempAlr LL alarm
set point
The sensor sensitivity is very low; repair the Hydran 201Ti's heating system.

12.1.24 Setup Lost

• Alarm type: Fail alarm
• Non-abbreviated description: Lost setup (configuration)
• Priority: Very high
• Parameter(s) involved: None
• Alarm cause(s): See below
Part 17997
Alarm Messages on the Hydran 201Ti's Display
Rev. 6, March 2011
12-13

Advertisement

Table of Contents
loading

Table of Contents