3.
Access the submenu Relays/Analog;GasHH Relay
4.
Set the parameter RelayMode of this relay to Normal.
5.
On the H201Ci-1, verify that:
• The two door-mounted push-button indicators (1 and 2) remain lit.
• The Alarm 1 (Gas High) indicator (yellow, DS10; item 15 in Figure 3-7 on page 3-12)
is off.
• The Alarm 2 (Gas High-High) indicator (yellow, DS9; item 14 in Figure 3-7 on
page 3-12) is off.
• The System OK indicator (yellow, DS11; item 16 in Figure 3-7 on page 3-12) is lit.
• The Alarm 1 NO contact is open.
• The Alarm 1 NC contact is closed.
• The Alarm 2 NO contact is open.
• The Alarm 2 NC contact is closed.
• The System OK alarm NO contact is closed.
• The System OK alarm NC contact is open.
• If connected, the SCADA system has detected the state change of both gas alarm relays.
Note: Pushing both buttons to acknowledge the gas alarm conditions should turn off the
indicators since the conditions have been cleared.
8.2.4.6

Conclusion

If necessary, set the parameter RelayMode of each alarm relay to their initial mode.
8.2.5

Verifying the RS-232 Communication

If your installation includes only one Hydran 201R Model i and if it communicates with the
host computer running the Hydran Host software, you must verify the RS-232 link. Proceed
as follows:
1.
Connect the Hydran 201Ci-1's RS-232 Computer Port connector (J10; item 7 in
Figure 3-7 on page 3-12) to your PC's RS-232 port. For wiring details, see Table
D-13 on page D-11. For USB users, connect the Hydran 201Ci-1's USB Computer
Port connector (J16; item 8 in Figure 3-7 on page 3-12).
Part 17997
Verification of Operation Prior to Installation
Rev. 6, March 2011
8-9