Communications With a Host Computer, Using an RS-232 Serial Communication
• In the H201Ci-1: To the terminals 21 to 24 of the Main Terminal Block (item 6 in
Figure 3-6 on page 3-11).
The installation of an RS-485 local network link cable is described in Section 9.5.1 on
page 9-9.
9.3
COMMUNICATIONS WITH A HOST COMPUTER, USING AN RS-232
SERIAL COMMUNICATION LINK
A Hydran 201Ti, a Hydran 201R Model i, a Hydran 201i System or a local network can be
connected, either locally or remotely (through a modem), to a host computer via an RS-232
serial communication link. Figure 9-2 on page 9-5 illustrates the various ways to connect a
host computer to a Hydran 201R Model i.
Host computer
DB-9

Figure 9-2 - Host Computer Connection Modes in a Hydran 201R Model i

The computer (or modem) can be attached to any Hydran 201Ci Controller on a local
network. General Electric Canada's Hydran Host software is the easiest way to
communicate directly with the H201Ci('s) or the network.
Note: A remote host computer can be used to supervise more than one local network of
Hydran 201i Systems.
The RS-232 serial communication link cable can be connected at the following locations:
• In the H201Ti: To the DB-9 Male RS-232 Connector (item 5 in Figure 2-2 on page 2-5)
on the back of the CPU module.
Part 17997
H201Ti
Supervisory link
isolated, 3 pairs;
max.: 1,200 m (4,000 ft)
Rev. 6, March 2011
H201C -1
i
RS-232
link
Modem
(option)
Host computer
Telephone
line
to remote
host computer
9-5