Adjusting The Temperature Set Point - GE Hydran 201 i Instruction Manual

Hide thumbs Also See for Hydran 201 i:
Table of Contents

Advertisement

5.
Compare the serial number displayed with the one located under the sensor's
connector (see item 3 in Figure 2-2 on page 2-5).
6.
Push ESC and DOWN to access Force Sensor Test.
7.
Push ENTER. The message AreYou Sure?;PressEnter.. is now displayed.
8.
Push ENTER again to confirm.
9.
When asked to enter the password #1 (1253), use the UP and ENTER keys.
10. The message Please wait... appears, the test is executed (during a four-second
countdown), and the H201Ti's display should indicate the message Good. If another
message is displayed, see Section 12.1.3 on page 12-2.
11. When all is done, push END. The Hydran 201Ti returns to the Main Display mode.
6.2.7

Adjusting the Temperature Set Point

1.
Allow 30 minutes after power-up for the temperatures to stabilize.
2.
Access the top of the extended menu by pushing ENTER twice (History appears).
Note: Once accessed, the extended menu times out after 30 minutes of keypad inactivity.
3.
Push DOWN twice until Temperatures appears.
4.
Access this menu by pushing ENTER.
5.
Push UP until Dyn Oil Sampl appears.
6.
Access this menu by pushing ENTER.
7.
Select Heater Power using the DOWN or UP key.
8.
Check the Heater Power is in the low percent range.
9.
Select Temp Setpoint using the DOWN or UP key.
10. Check the Temp Setpoint is 35 °C (95 °F), the default value.
Part 17997
Verification of Operation Prior to Installation
Rev. 6, March 2011
6-13