4.2.5.2

Short Power-up (Power-off Shorter Than Five Minutes)

In this sequence, the self-test is not executed. After the message System;Initialization, the
Main Display mode is immediately displayed.
4.2.5.3

First Power-up (After Reconnection of Battery)

In this sequence, the H201Ti requests the values listed in Table 4-3 on page 4-7 before
executing the self-test sequence. The Main Display mode is then displayed (the H201Ti
will not be in service until these values are entered).

Table 4-3 - Values Requested During the First Power-up Sequence

Display
Enter Date&Time
Year
Month
Day
Hour
Minute
a
PowerStat. ID
a
H201Ti ID
a.
For details on these parameters, see Section 4.5.6.5 on page 4-23.
Note: The dialog of the first power-up can only be performed using the H201Ti's keypad,
not the Hydran Host software.
4.3

USING THE KEYPAD'S KEYS ACCORDING TO EACH MODE

The Hydran 201Ti's keypad is shown in Figure 4-2 on page 4-8. Table 4-4 on page 4-8
summarizes the functions of the keys according to the operating modes.
Part 17997
Using the Keypad's Keys According to Each Mode
Data Entry
Press ENTER
Start the dialog
(Year)
(Month)
(Day)
Enter the requested value
(Hour)
(Minute)
Absolutely enter a number (1 to 9999)
0
Absolutely enter a number (1 to 254)
Rev. 6, March 2011
Action
4-7