Chapter 8 • Hydran 201Ci-1 Installation
2.
In the Communication submenu of the Hydran 201Ti, write down the current
settings, in order to be able to restore them.
3.
Set the parameters as follows:
• Comm Channel = Supervisory Link
• Default Channel = Supervisory Link
• Baud Rate = 9600
• Gas Monitor ID = 1
4.
To establish the communication, start the Hydran Host software on the PC. See the
Hydran Host Software Manual for more information.
5.
If the communication cannot be established:
• Ensure the H201Ti identification number entered in the Hydran Host software
corresponds to the one entered in the H201Ti (Gas Monitor ID parameter).
• Verify the wiring of the supervisory link cable.
• Verify the configuration of the Hydran Host software. See the Hydran Host Software
Manual for more information.
6.
Disconnect all communication cables (supervisory link and RS-232 to the PC).
7.
When the test is completed, restore the original communication settings in the
H201Ti as noted in the step 2 above.
8.2.6
Conclusion
This completes the incoming verification of the Hydran 201Ci-1.
1.
Disconnect the H201Ti from the power outlet.
2.
Disconnect the H201Ci-1 from the power outlet.
3.
Remove all supply cables.
4.
Remove all communication cables.
5.
Store the H201Ti and the H201Ci-1 in their respective boxes, ready for installation.
8-10
Rev. 6, March 2011
Part 17997