6
Connecting Water Pipes

Connecting the Humidifier Water Inlet Pipe

6.1
G 3/4 inch reserved connector
with outer screw thread
G 3/4 inch adapter with inner screw thread
Matched with the adapter, the pressure
resistance should be at least 0.7 MPa
Note 1:
1. When plastic materials such as PA66 are used, the recommended torque is 5 N.m.
2. When metal materials are used, the recommended torque is 10 N.m. A sealing washer
must be used when an union is used.

Connecting the Drainpipe

6.2
Connection method
NetCol8000-A045/A055/A090 Downflow
1
(1) Connector with inner
screw threads
(2) Rigid pipe adapter
(3) Rigid pipe
The drainpipe from indoor unit to condensate
branch pipe must have gradients (>1: 100).
Significant upward trend and stagnant water
is not allowed along the pipe.
NetCol8000-A045 Upflow
16
(4) Pagoda connector
(5) Hose clamp
(6) Hose