Mitsubishi Electric MELSEC-Q Series User Manual page 80

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

(2) Terminal block of the master/local module
(a) Solderless terminal
Use a solderless terminal and wire specified in the following table. Tighten a solderless terminal within the
specified torque range. Use a UL-listed solderless terminal and a tool recommended by the manufacturer of
the solderless terminal for processing.
Solderless terminals with sleeves cannot be used.
Solderless terminal
Model
name
1.25-3
(b) Screws and tightening torque
The table below lists the screws of the terminal block and the tightening torque.
Terminal block screw (M3 screw)
Terminal block mounting screw (M3.5 screw)
(3) Wiring check
Connect the master station with the slave station. Check whether the slave station is turned on and off by turning
on and off the device of the master station. (
78
Tightening torque range
0.42 to 0.58N•m
Screw type
Diameter
Type
22 to 16AWG
Stranded
Tightening torque range
Page 59, Section 4.1)
Wire
Temperature
Material
rating
Copper
60°C or higher
0.42 to 0.58N•m
0.66 to 0.89N•m