Mitsubishi Electric MELSEC-Q Series User Manual page 118

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Item
Set the mode for a master/local module. (
3.6.2 to Page 51, Section 3.6.5)
Mode
Set the same mode as a master station to use a master/local module
as a standby master station.
The setting is not required when a master/local module is used as a
Total Module
local station or standby master station. (Except when "Master
Connected
Station(Duplex Function)" is selected for "Type")
Set the start device where RX, RY, RWr, and RWw are transferred. By
Remote Input(RX)
setting these items, RX, RY, RWr, and RWw can be automatically
transferred to a device in a CPU module without using a program.
(1)
Remote Output(RY)
(2)
Remote Register(RWr)
(3)
(4)
Remote Register(RWw)
116
Description
Number of refresh points
All points for the station number 1 to last station number are
automatically assigned. (
55, Section 3.6.6)
To use a different refresh device for each station, transfer the
device individually using a program (Un\G or FROM/TO
instructions).
The points for each station can be checked using Slave station
offset, size information (Un\G992 to Un\G1503). (
335, Appendix 2 (4))
Buffer memory areas of the refresh sources (
Section 3.6.3 (2), Page 50, Section 3.6.4 (3), Page 56, Section
3.6.6 (3))
• When "Remote Net(Ver.1 Mode)" or "Remote Net(Additional
Mode)" is set to "Mode"
Data in Ver.1-compatible area are transferred to a CPU
module.
• When "Remote Net(Ver.2 Mode)" is set to "Mode"
Data in Ver.2-compatible area are transferred to a CPU
module.
Overlaps with other devices
Set the devices without overlaps with the following.
• Refresh parameters of modules on the network
• I/O numbers used for I/O modules and an intelligent function
module
• Auto refresh settings of an intelligent function module
• Auto refresh using a multiple CPU shared memory
Refresh timing
Data are refreshed in the END process of a CPU module.
Page 43, Section
Page 46, Section 3.6.3 to Page
Page
Page 47,
Setting range
• Remote Net(Ver.1 Mode)
• Remote Net(Ver.2 Mode)
• Remote Net(Additional Mode)
• Offline
(Default: Remote Net(Ver.1 Mode))
Blank or the following range
• Device
X, M, L, B, D, W, R, or ZR
(M, B, D, and W for a MELSECNET/H
remote I/O station)
• Device No.
Within the device range of the CPU
module or MELSECNET/H remote
I/O station
(Default: Blank)
Blank or the following range
*1
• Device
Y, M, L, B, T, C, ST, D, W, R, or ZR
(M, B, D, and W for a MELSECNET/H
remote I/O station)
• Device No.
Within the device range of the CPU
module or MELSECNET/H remote
I/O station
(Default: Blank)
Blank or the following range
• Device
M, L, B, D, W, R, or ZR
(M, B, D, and W for a MELSECNET/H
remote I/O station)
• Device No.
Within the device range of the CPU
module or MELSECNET/H remote
I/O station
(Default: Blank)
Blank or the following range
• Device
M, L, B, T, C, ST, D, W, R, or ZR
(M, B, D, and W for a MELSECNET/H
remote I/O station)
• Device No.
Within the device range of the CPU
module or MELSECNET/H remote
I/O station
(Default: Blank)