Mitsubishi Electric MELSEC-Q Series User Manual page 370

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

When the transmission speed is 10Mbps in the following system configuration (It is assumed that there is
Ex.
no faulty station, transient transmission, and retry in this example.)
Master station
Station number 1
Remote I/O station
BT = 0.8
NI = 12 16
NW = 11 16
N = 5
ni = 12
nw = 10
LS = 0.8{27 + (16 × 4.8) + (16 × 9.6) + (5 × 30) + (12 × 4.8) + (10 × 9.6)} + 2300 + 160
= 2908.8µs
= 2.91ms
368
*1
Station number 2
Remote device station
*1: The number of
*2: The number of
occupied stations: 1
ST = 2300
1) 800 + (12 × 15) = 980
2) 900 + (3 × 50) = 1050
3) 1200 + (11 × 100) = 2300
A = 12, B = 3, C = 11
Station number 4
*2
Intelligent device station
*3: The number of
occupied stations: 2,
occupied stations: 4,
expanded cyclic
expanded cyclic
setting: Quadruple
setting: Single
*3
Station number 8
Local station
*3
Station number 12
Remote I/O station
EX = 50 + 110 × 1 = 160
*1