3.2.2

Maximum overall cable distance (CC-Link Ver.1.10)

This section describes how transmission speed and a cable length are related when a system is configured with
products of CC-Link Ver.1.10 or later and Ver.1.10-compatible CC-Link dedicated cables. Configure a CC-Link system
that satisfies the following conditions.
Master station
• Ver.1.10-compatible CC-Link dedicated cable (a terminating resistor of 110 used)
Transmission speed
156kbps
625kbps
2.5Mbps
10Mbps
Remote I/O station
Remote I/O station
or remote
or remote
device station
device station
Station-to-station cable length
Maximum overall cable distance
Station-to-station cable length
5Mbps
Local station or
intelligent device
station
Maximum overall cable distance
20cm or longer
CHAPTER 3 SPECIFICATIONS
Local station or
intelligent device
station
1200m
900m
400m
160m
100m
29