Mitsubishi Electric MELSEC-Q Series User Manual page 349

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Number
Name
SB006D
Parameter setting
(5E6
, b13)
status
H
SB006E
Host station operating
(5E6
, b14)
status
H
Setting status of block
SB006F
guarantee of cyclic
(5E6
, b15)
H
data per station
SB0070
Master station
(5E7
, b0)
information
H
SB0071
Standby master
(5E7
, b1)
station information
H
SB0072
Scan mode setting
(5E7
, b2)
information
H
Operation
SB0073
specification when
(5E7
, b3)
H
CPU is down status
SB0074
Reserved station
(5E7
, b4)
specified status
H
SB0075
Error invalid station
(5E7
, b5)
specified status
H
Description
Whether the parameters have been correctly set is stored.
OFF: Correct
ON: Setting incorrect (An error code is stored in
SW0068.)
Whether data link with other stations is being performed is
stored.
OFF: In process
ON: Not performed
Whether the block guarantee of cyclic data per station has
been set to the host station is stored.
OFF: Not set
ON: Set
Data link status is stored.
OFF: Data link control by the master station
ON: Data link control by the standby master station
Whether a standby master station exists is stored.
OFF: Absence
ON: Present
The setting status of the scan mode is stored.
OFF: Asynchronous mode
ON: Synchronous mode
The parameter setting status of the operation specification
when CPU is down is stored.
OFF: Stopped
ON: Continued
Whether a reserved station has been specified by the
parameter is stored.
OFF: Not specified
ON: Specified (The set station number is stored in
SW0074 to SW0077.)
Depending on the link refresh timing, SB0074 may be
updated with the time difference of one sequence scan
from the update of Reserved station specified status
(SW0074 to SW0077).
Whether an error invalid station has been specified using
the parameter is stored.
OFF: Not specified
ON: Specified (The set station number is stored in
SW0078 to SW007B.)
Depending on the link refresh timing, SB0075 may be
updated with the time difference of one sequence scan
from the update of Error invalid station specified status
(SW0078 to SW007B).
APPENDICES
Availability
( : Yes, ×: No)
Online
Offline
Master
Local
station
station
(For the
×
×
station
number 0
only)
×
×
×
×
×
×
×
×
×
347