Item
Set the start device where RX, RY, RWr, and RWw are
transferred. By setting these items, RX, RY, RWr, and RWw can
be automatically transferred to a device in a CPU module without
Remote Input(RX)
using a program.
(1)
Number of refresh points
All points for the station number 1 to last station number are
automatically assigned. (
Page 55, Section 3.6.6)
To use a different refresh device for each station, transfer
the device individually using a program (Un\G or
FROM/TO instructions).
The points for each station can be checked using Slave
Remote Output(RY)
station offset, size information (Un\G992 to Un\G1503).
(
(2)
Buffer memory areas of the refresh sources (
47, Section 3.6.3 (2),Page 50, Section 3.6.4 (3), Page 56,
Section 3.6.6 (3))
• When "Remote Net(Ver.1 Mode)", "Remote Net(Additional
Mode)", or "Remote I/O Net Mode" is set to "Mode"
Data in Ver.1-compatible area are transferred to a CPU
module.
Remote
• When "Remote Net(Ver.2 Mode)" is set to "Mode"
Register(RWr)
Data in Ver.2-compatible area are transferred to a CPU
module.
(3)
Overlaps with other devices
Set the devices without overlaps with the following.
• Refresh parameters of modules on the network
• I/O numbers used for I/O modules and an intelligent
function module
• Auto refresh settings of an intelligent function module
Remote
• Auto refresh using a multiple CPU shared memory
Register(RWw)
(4)
Refresh timing
Data are refreshed in the END process of a CPU module.
When "Remote Net(Additional Mode)" is set to "Mode", set the
Ver.2 Remote
start device where RX, RY, RWr, and RWw (Ver.2-compatible
Input(RX)
area) of a master/local module are transferred.
(1)
Number of refresh points
All points for the start station number to last station number
Ver.2 Remote
of a Ver.2-compatible slave station are automatically
Output(RY)
assigned. (
To use a different refresh device for each station, transfer
the device individually using a program (Un\G or
Ver.2 Remote
FROM/TO instructions).
Register(RWr)
The points for each station can be checked using Slave
station offset, size information (Un\G992 to Un\G1503).
(
Ver.2 Remote
The other contents are same as those for "Remote Input(RX)"
Register(RWw)
described the above.
Description
Page 46, Section 3.6.3 to
Page 335, Appendix 2 (4))
Page 54, Section 3.6.5 (3))
Page 335, Appendix 2 (4))
CHAPTER 7 PARAMETER SETTINGS
Setting range
Blank or the following range
• Device
X, M, L, B, D, W, R, or ZR (M, B, D, and W for
a MELSECNET/H remote I/O station)
• Device number
Within the device range of the CPU module
or MELSECNET/H remote I/O station
(Default: Blank)
Blank or the following range
*1
• Device
Y, M, L, B, T, C, ST, D, W, R, or ZR
(M, B, D, and W for a MELSECNET/H remote
I/O station)
• Device number
Within the device range of the CPU module
Page
or MELSECNET/H remote I/O station
(Default: Blank)
Blank or the following range
• Device
M, L, B, D, W, R, or ZR (M, B, D, and W for a
MELSECNET/H remote I/O station)
• Device number
Within the device range of the CPU module
or MELSECNET/H remote I/O station
(Default: Blank)
Blank or the following range
• Device
M, L, B, T, C, ST, D, W, R, or ZR
(M, B, D, and W for a MELSECNET/H remote
I/O station)
• Device number
Within the device range of the CPU module
or MELSECNET/H remote I/O station
(Default: Blank)
Same as "Remote Input(RX)"
Same as "Remote Output(RY)"
Same as "Remote Register(RWr)"
Same as "Remote Register(RWw)"
7