Mitsubishi Electric MELSEC-Q Series User Manual page 102

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Item
Special Relay(SB)
Set the start device where SB and SW are transferred. SB and
SW can be automatically transferred to a device in a CPU module
without using a program.
Special
Register(SW)
Retry Count
Set the number of retries when a communication failure occurs.
Set the number of slave stations that return to the system
Automatic
operation by a single link scan after the stations are disconnected
Reconnection
due to a communication failure.
Station Count
Setting a larger number extends link scan time of when the
station returns.
Set the station number for the standby master station.
Set the number of the station that controls a CC-Link system
Standby Master
instead of the master station if a master station goes down.
Station No.
(
Select whether to stop or continue data link if a stop error occurs
PLC Down Select
in a CPU module. (
Whether to synchronize the link scan with the sequence scan of a
CPU module or not can be selected. (
8.3.5)
• Asynchronous
A link scan does not synchronize with a sequence scan. Input
transmission delay time is shortened.
Scan Mode Setting
• Synchronous
A link scan synchronizes with a sequence scan. (The
sequence scan and link scan start simultaneously.)
Output transmission delay time is shortened.
Because of the synchronization, extended sequence scan time
increases link scan time.
Delay Time Setting
Set 0.
Set information about a slave station connected to the master
Station Information
Setting
station. (
Set the procedure for the initial settings when registering the
Remote Device
initial settings of a remote device station using a programming
Station Initial Setting
tool. (
Set the conditions used to issue a request for the interrupt to a
Interrupt Settings
CPU module. (
*1
The operations when the switch on a CPU module is set to STOP vary depending on whether Y or the devices other
than Y is set to "Remote Output(RY)". (
*2
The ranges can be set only for the Redundant CPU.
100
Description
Page 135, Section 8.2.5)
Page 130, Section 8.2.2)
Page 102, Section 7.3.2 (2))
Page 108, Section 7.3.2 (3))
Page 111, Section 7.3.2 (4))
Blank or the following range
• Device
M, L, B, D, W, R, SB, or ZR
(M, B, D, W, and SB for a MELSECNET/H
remote I/O station)
• Device number
Within the device range of the CPU module
or MELSECNET/H remote I/O station
• (Default: Blank)
Blank or the following range
• Device
M, L, B, D, W, R, SW, or ZR
(M, B, D, W, and SW for a MELSECNET/H
remote I/O station)
• Device number
Within the device range of the CPU module
or MELSECNET/H remote I/O station
(Default: Blank)
1 to 7 (Default: 3)
1 to 10 (Default: 1)
• Blank
• 1 to 64
(Default: Blank)
• Stop
• Continue
(Default: Stop)
Page 163, Section
• Asynchronous
• Synchronous
(Default: Asynchronous)
Page 133, Section 8.2.4)
Setting range
0