Mitsubishi Electric MELSEC-Q Series User Manual page 212

Cc-link system master/local module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

(2) Functions
(a) Operation chart of the G(P).RLPASET instruction
Command
Device
4.
1.
The network parameters set in (S1) to (S5) are transferred to the master station specified by Un.
2.
The master station analyzes the settings of the network parameters.
3.
If the network parameter settings are correct, the data link is started.
4.
The device specified by (D) turns on.
(b) Simultaneous execution of the G(P).RLPASET instruction
Two or more G(P).RLPASET instructions cannot be executed simultaneously.
(c) Check of the completion status
There are two types of interlock signals for the G(P).RLPASET instruction: Completion device (D) and Status
display device at completion (D) + 1.
• Completion device
Turns on in the END process of the scan where the G(P).RLPASET instruction is completed, and turns off
in the next END process.
• Status display device at completion
Turns on and off depending on the completion status of the G(P).RLPASET instruction.
Normal completion:
Abnormal end:
210
CPU module
G(P).RLPASET
1.
Execution result
Remains off and does not change.
Turns on in the END process of the scan where the G(P).RLPASET instruction is
completed, and turns off in the next END process.
Master station
Network
parameter
2.
3.
Data link start