Item
Select the station type. Set the station type of the slave station actually
Station Type
connected.
Select CC-Link version of the slave station.
Select the mode of the master/local module if the slave station is a
master/local module.(
Version
3.6.5)
Select the same CC-Link version as the version of the slave station
actually connected. If not, data link cannot be performed.
# of STA Occupied
Select the number of occupied stations of the slave station.
Expanded Cyclic
Select the expanded cyclic setting for the slave station. The setting
Setting
can be selected only when "Ver.2" or "Add" is set to "Version".
The number of points of remote I/O (RX, RY) occupied by the slave
station is displayed.
The number of points can be changed for a remote I/O station when
"Ver.2 Mode" is set to "Mode Setting". Changing the number of points
can save the areas of a refresh device in a CPU module.(
170, Section 8.3.9)
When setting eight points to the remote I/O stations, set them to even
numbers of the stations consecutively. When setting eight points to
Remote Station Points
odd numbers of the remote I/O stations, set "8 Points+8
Points(Reserved)" to the last of consecutive remote I/O stations.
Master station
Remote output (RY)
Station No.2 Station No.1
Empty
"8 Points+
8 Points
(Reserved)"
Select whether to set the slave station as a reserved station or an
Reserved/Err Invalid
error invalid station. (
STA
Section 8.3.6)
Set the size of buffer memory used to perform transient transmission
Intelligent Buffer
with dedicated instructions. This setting can be configured only for a
Size(word)
local station, intelligent device station, and standby master station.
Set the size of send buffer to send data using the G(P).RIWT
Send
instruction.
Set the size of receive buffer to receive data using the G(P).RIRD
Receive
instruction.
Set the size of automatic update buffer to communicate with an
Auto
intelligent device station using automatic update buffer.
Set the size required for each intelligent device station.
Set the station-specific mode for the slave station. This setting can be
Station-specific mode
configured only when the slave station supports the station-specific
setting
mode.
Description
Page 43, Section 3.6.2, Page 51, Section
Remote I/O station
Remote I/O station
(Station No.1, no. of
(Station No.2, no. of
occupied stations: 1)
occupied stations: 1)
Y07 to Y00
Station No.3
8-point output
module
Page 162, Section 8.3.4, Page 167,
Page
Remote I/O station
(Station No.3, no. of
occupied stations: 1)
Y07 to Y00
Y07 to Y00
8-point output
8-point output
module
module
CHAPTER 7 PARAMETER SETTINGS
Setting range
Varies depending on the module that
was set.
Varies depending on the module that
was set.
Varies depending on the module that
was set.
Varies depending on the module that
was set.
• 0 Point (Reserved Station)
• 8 Points
• 8 Points+8 Points(Reserved)
• 16 Points
• 32 Points
(Default: Varies depending on the
number of occupied stations)
• No Setting
• Reserved Station
• Error Invalid Station
(Default: No Setting)
0, 64 to 4096
Note that the total buffer size of "Send"
and "Receive" for all slave stations must
be 4096 or less.
(Default: 64)
0, 128 to 4096
Note that the total buffer size of "Auto"
for all slave stations must be 4096 or
less.
(Default: 128)
Varies depending on the module that
was set.
7
105