Check whether data link is being performed normally.
Turning on Y1000 of the master station on "Device/Buffer Memory Batch" on the programming tool turns
on RY0 (Y0) of the AJ65BTB2-16T (station number 1).
Turning on X0 of the AJ65BTB1-16DT (station number 2) turns on X1020 of the master station.
[Online]
Turn on Y1000 in the master station.
*1
The LED may look dimly lit or off depending on the communication status.
● If the operation above does not turn on the output (Y) of the slave station or the input (X) of the master station, check the
RX, RY, RWr, and RWw assignment of the module using Slave station offset, size information (Un\G992 to Un\G1503).
● Before turning on or off the output using a device test, ensure the safety of the external device. Failure to do so may
break the external device or cause an accident.
16.
When the connection status is normal, create a control program. (
Write the program to the CPU module. Then reset the CPU module or power off and on the system.
68
[Monitor]
[Device/Buffer Memory Batch]
RY0 in the AJ65BTB2-16T is turned on.
This LED is turned on.
Page 228, CHAPTER 10)
: ON
: Flashing *1
: OFF