Item
Select whether to actually execute the registered procedure or not.
Click it to change the setting.
Execute Flag
Set "Only Set" to use the setting only as a reference when inputting
similar setting items.
Select whether to newly set the condition for the initial settings or use
Operational Condition
the same condition as the above line.
Executional Condition
Set the condition to execute the initial settings.
Condition Device
Select the device to execute the initial settings.
Set the device number of the device set to "Condition Device". Set 0 to
the first device number for each station.
Ex.
For instance, 0 to 1F can be set to the device number for the
station number 4 as shown below.
Device No.
Select whether to execute the initial settings with ON of the condition
Execute Condition
device or with OFF of the condition device.
5.
When completing the initial settings, write the settings to the CPU module using a programming
tool.
[Online]
6.
The settings are reflected by resetting the CPU module or powering off and on the system.
7.
Start the initial settings by turning on Remote device station initialization procedure registration
instruction (SB000D).
While the initial settings are being executed, Execution status of remote device station initialization
procedure (SB005E) is on.
Also the execution procedure number and the target station number for the procedure registration are
stored in Remote device station initialization procedure registration execution individual information
(SW0110 to SW011F).
8.
When the initial settings are completed for all the set stations, Completion status of remote device
station initialization procedure (SB005F) is turned on.
Also the execution results are stored in Remote device station initialization procedure registration
instruction result (SW005F).
The data stored in Remote device station initialization procedure registration execution individual
information (SW0110 to SW011F) become FF**
settings.)
9.
Turn off Remote device station initialization procedure registration instruction (SB000D).
Remote device station initialization procedure registration instruction result (SW005F) and Remote device
station initialization procedure registration execution individual information (SW0110 to SW011F) are
cleared.
Description
Remote device station
(Station No.1, no. of
Master station
occupied stations: 3)
RX0
RX0
Station No.1
RX5F
RX5F
RX60
Station No.4
RX7F
[Write to PLC]
CHAPTER 7 PARAMETER SETTINGS
• Execute
• Only Set
(Default: Execute)
• Set New
• Same as Prev. Set
(Default: Set New)
• RX
• SB
(Default: Blank)
• For RX: 0 to 37F
Remote device station
(Station No.4, no. of
• For SB: 0 to FF
occupied stations: 1)
(Default: Blank)
RX0
RX1F
• ON
• OFF
(Default: Blank)
. ("**" indicates the target station number for the initial
H
Setting range
-
H
H
109
7