 Automatic connection system configuration
 GOT2000 series automatic recognition
• When the GOT2000 series is connected, the parameters required for the GOT connection are automatically changed by
setting the automatic recognition on the GOT2000 series side.
• Set the station number (Pr.117 or Pr.331) of the inverter before the automatic recognition is performed.
• Connect all the stations of inverters with GOT before the automatic recognition is performed. The inverter newly added
after automatic recognition will not be recognized automatically. (When an inverter is added, perform the initial setting in
Pr.999 Automatic parameter setting or set the automatic recognition on the GOT side again.)
Automatic change item
Communication speed
Data length / stop bit
Parity
Waiting time setting
CR/LF selection
Number of communication
retries
Communication check
time interval
Protocol selection
NOTE
• If the automatic recognition cannot be performed, initial setting in Pr.999 is required.
• For connection to a device other than the GOT2000 series, initial setting in Pr.999 is required.
• For details, refer to the GOT2000 Series Connection Manual (Mitsubishi Product).
Parameters referred to
Pr.999 Automatic parameter

5.15.10 Backup/restore

The GOT can be used for backing up inverter parameters and the data used in the PLC function of inverter.
The backup data stored in the GOT can be used to restore the data in the inverter.
Pr.
434
Network number (CC-Link
*1
IE)
N110
435
Station number (CC-Link IE) 0
*1
N111
*1
The setting is available in the inverter on which the FR-A8NCE is installed or when the FR-A800-GF inverter is used.
668
5. PARAMETERS
5.15 (N) Communication operation parameters
Four-wire multidrop
GOT2000
Automatic change parameter
PU connector connection
Pr.118
Pr.119
Pr.120
Pr.123
Pr.124
Pr.121
Pr.122
(Pr.549 holds the value before
the automatic recognition.)
settingpage 333
Initial
Name
value
0
RS-485 terminal connection
Pr.332
Pr.333
Pr.334
Pr.337
Pr.341
Pr.335
Pr.336
Pr.549
Setting range
0 to 255
Enter the network number of the inverter.
0 to 255
Enter the station number of the inverter.
Terminating resistor
Setting value after change
Depending on the setting of the connected
device on the GOT side.
9999 (fixed)
9999 (fixed)
0 (fixed to Mitsubishi inverter protocol)
Description