Online Auto Tuning - Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

Parameters referred to
Pr.9 Electronic thermal O/L
relaypage 394
Pr.71 Applied
motorpage 505
Pr.178 to Pr.189 (Input terminal function
Pr.800 Control method
selectionpage 215

5.13.4 Online auto tuning

Magnetic flux
Magnetic flux Sensorless
Magnetic flux
Sensorless
Sensorless Vector
Vector
Vector
If online auto tuning is selected under Advanced magnetic flux vector control, Real sensorless vector control, or Vector control,
favorable torque accuracy is retained by adjusting temperature even when the resistance value varies due to increase in the
motor temperature.
Pr.
Name
95
Online auto tuning selection
C111
574
Second motor online auto tuning
C211
 Online auto tuning at startup (Pr.95/Pr.574 = "1")
• By promptly tuning the motor status at startup, accurate operation without being affected by motor temperature is achieved.
Also high torque can be provided at very low speed and stable operation is possible.
• Under Advanced magnetic flux vector control (Pr.80 Motor capacity, Pr.81 Number of motor poles) or Real sensorless
vector control
(Pr.80, Pr.81, Pr.800 Control method selection), select the online auto tuning at start.
• Make sure to perform offline auto tuning before performing online auto tuning.
Operating procedure
1.
Perform offline auto tuning. (Refer to
2.
Check that Pr.96 Auto tuning setting/status = "3 or 103" (offline auto tuning completion).
3.
Set Pr.95 Online auto tuning selection = "1" (online auto tuning at start).
Online auto tuning is enabled at the next start.
4.
Check that the following parameters are set before starting operation.
Pr.
9
71
80
81
*1
If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies may deteriorate due
to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
5.
In the PU operation mode, press
For External operation, turn ON the start command (STF signal or STR signal).
selection)page 496
Initial value
0
0
1
2
0
0 to 2
page
509.)
Rated motor current or electronic thermal O/L relay
Applied motor
Motor capacity (with the rated motor current equal to or less than the inverter rated current)
Number of motor poles
/
on the operation panel.
Setting range
No online auto tuning
Online auto tuning is performed at startup.
Magnetic flux observer (continuous tuning)
Select online auto tuning for the second motor.
(The settings are the same as those in Pr.95.)
Description
5.13 (C) Motor constant parameters
Description
*1
527
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10