Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 614

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

NOTE
• The undervoltage avoidance function is invalid under torque control by Real sensorless vector control. When Pr.261="11 (12)",
the operation is performed in the same manner as Pr.261="1 (2)".
 Automatic adjustment of deceleration time (Pr.261 = "21 or 22", Pr.294,
Pr.668)
• When "21 or 22" is set to Pr.261, the deceleration time is automatically adjusted to keep (DC bus) voltage constant in the
converter when the motor decelerates to a stop at a power failure. Setting of Pr.262 to Pr.266 is not required.
• If a phenomenon such as motor vibration occurs during operation of the deceleration time automatic adjustment function,
adjust the response level by setting the Pr.668 Power failure stop frequency gain. Increasing the setting improves the
response to change in the bus voltage. However, the output frequency may become unstable.
• If setting Pr.294 UV avoidance voltage gain lower also does not suppress the vibration, set Pr.668 lower.
Pr.261 = 21
Power
supply
During deceleration at
occurrence of power failure
Deceleration time : Automatic adjustment
Output
frequency
During stop at occurrence
of power failure
STF
Turn OFF STF once to make acceleration again
Y46
 Deceleration stop by the Power failure stop external(X48) signal
• By turning OFF X48 signal, the power failure time deceleration-to-stop function is activated. This function is used, for
example, when an external power failure detection circuit is installed.
• To use the power failure time deceleration-to-stop function for the separated converter type, use X48 signal. Connect the
terminal to which PWF signal of the converter unit is assigned and the terminal to which X48 signal of the inverter is
assigned.
• In the initial setting, X48 signal is used with the normally closed (NC contact) input specification. Use Pr.606 Power failure
stop external signal input selection to change the specification to the normally open (NO contact) input.
• To use the X48 signal, set "48" in any of Pr.178 to Pr.189 (Input terminal function selection) to assign the function to
an input terminal.
 During deceleration at occurrence of power failure (Y46) signal
• After deceleration by a power failure, the inverter is not restarted even though the start command is input. Check the During
deceleration at occurrence of power failure (Y46) signal at a power failure. (For example, when input phase loss protection
(E.ILF) occurs.)
• The Y46 signal is turned ON during deceleration at occurrence of power failure and in a stop status after deceleration at
occurrence of power failure.
• For the Y46 signal, set "46 (positive logic)" or "146 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function
selection) to assign the function.
 Power failed (Y67) signal
• The Y67 signal turns ON when the output is shut off due to detection of power failure (power supply fault) or undervoltage,
or the power failure time deceleration-to-stop function is activated.
• To use the Y67 signal, assign the function by setting "67 (positive logic)" or "167 (negative logic)" in any of Pr.190 to Pr.196
(output terminal function selection).
Time
5. PARAMETERS
5.14 (A) Application parameters
1
2
3
4
5
6
7
8
9
10
613

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents