5.14.2 Self power management

V/F
V/F
V/F
Magnetic flux
Magnetic flux
Magnetic flux
By turning ON the magnetic contactor (MC) on the input side before the motor is started and turning OFF the MC after the motor
is stopped, power is not supplied to the main circuit, reducing the standby power.
Pr.
Name
248
Self power management
A006
selection
137
Start waiting time
A002
254
Main circuit power OFF
A007
waiting time
30
Regenerative function
E300
selection
 Connection diagram
• Terminal R1, S1 inputs
MCCB
MC1
R/L1
S/L2
T/L3
R1/L11
S1/L21
Standard models
538
5. PARAMETERS
5.14 (A) Application parameters
ON
OFF
During inverter operation: MC2-OFF, MC3-ON
During commercial power supply operation: MC2-ON, MC3-OFF
timepage 681
597,
page 604
selection)page 496
selection)page 450
PM
PM
PM
Initial
value
0
1
0
2
0.5 s
0 to 100 s
1 to 3600 s
600 s
9999
100, 101
0
0 to 2, 10,
11, 20, 21,
102, 110,
111, 120,
121
Inverter
U
M
V
W
MC1
MC1
24VDC
SE
MC operation
Setting
range
Self power management function disabled
Self power management function enabled (main circuit OFF at protective
function activation)
Self power management function enabled (main circuit OFF at protective
function activation due to a circuit failure)
Set a time period that is a little longer than the time period from the ON
signal input to the actual pick-up operation of MC1 (0.3 to 0.5 s).
Set the waiting time until the main circuit power supply is turned OFF
after the motor is stopped.
The main circuit power supply is turned OFF only when the protective
function selected by Pr.248 is activated.
Power supply to the inverter: AC (terminals R, S, and T)
When power is supplied only to the control circuit, and then switched to
be supplied to both the control and main circuits, inverter reset is not
performed.
For other settings, refer to
Converter unit
MCCB
MC1
R/L1
S/L2
T/L3
R1/L11
S1/L21
Separated converter type
Description
page
689.
Inverter
P/+
P/+
U
N/-
N/-
V
W
RDA
X10
RSO
RES
Y17
X94
MC1
SE
SD
R1/L11
S1/L21
SE
M
MC1
24VDC

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents