Instructions - Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

The reply code (RWr10) to the instruction code execution is set in D2. (Refer to
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302 X1025
16
24
 Programming example for resetting the inverter at an inverter fault
The following program resets the station 1 inverter at an inverter fault.
SB49
SW0B0.0
0
M0 X103A X20
3
Error status flag
7
NOTE
• The inverter reset with the flag RY3A shown above is enabled at an inverter fault only.
• When Pr.349 Communication reset selection = "0", inverter reset is available independently of the operation mode.
• When using the instruction code execution request (RY25) with the instruction code (HFD) and data (H9696) to reset the
inverter, set a value other than "0" in Pr.340 Communication startup mode selection or change the operation mode to the
Network operation mode. (For the program example, refer to

5.21.6 Instructions

 Programming instructions
• Since the buffer memory data of the master station is kept transferred (refreshed) to/from the inverters, the TO instruction
need not be executed every scan in response to data write or read requests. (The execution of the TO instruction every
scan does not pose any problem.)
• If the FROM/TO instruction is executed frequently, data may not be written reliably. When transferring data between the
inverter and sequence program via the buffer memory, perform the handshake to confirm that data has been written
without error.
TO instruction
Correct
Write completion
M0
Check the data link status of the station 1.
PLS
M300
SET M301
Write the faults history No.1 and No.2 read
MOV H74
W110
code (H74) to RWw10.
SET Y1025
Turn ON the instruction code execution request
(RY25).
RST M301
SET M302
MOV W11 D1
Read the fault record (RWr11) and the reply code
(RWr10) to output to D1 and D2 when the instruction
code execution completion (RX25) turns ON.
MOV W10 D2
Turn OFF the instruction code execution request
RST Y1025
(RY25).
RST M302
END
M0
Check the data link status of the station 1.
Turn ON the error reset request flag (RY3A).
Y103A
Turn OFF the error reset request flag (RY3A)
when the error status flag (RX3A) is OFF.
END
page
TO instruction
Incorrect
Write completion
page 724
for the reply code (RWr10).)
729.)
5.21 CC-Link IE Field Network (FR-A800-GF)
1
2
3
4
5
6
7
8
9
10
733