Setting Procedure Of Real Sensorless Vector Control (Torque Control) - Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

The following diagram indicates operation relative to commands given by analog input via terminal 1.
Speed
Speed
Speed
Speed
STF
(Forward
rotation
command)
OL
• At the STF signal ON, the speed limit value is raised in accordance with the setting of Pr.7.
• Speed control is performed when the actual speed exceeds the speed limit value.
• At the STF signal OFF, the speed limit value is lowered in accordance with the setting of Pr.8.
• Under torque control, the actual operation speed is a constant speed when the torque command and load torque are
balanced.
• The direction of motor torque generation is determined by a combination of the input torque command polarity and the start
signal, as given in the following table.
Polarity of torque
command
Forward direction (forward
+ torque command
power driving / reverse
regenerative driving)
Reverse direction (forward
- torque command
regenerative driving / reverse
power driving)
NOTE
• Once the speed limit is activated, speed control is performed and internal torque limit (Pr.22 Torque limit level) is enabled.
(Initial value) In this case, it may not be possible to return to torque control.
Torque limit should be external torque limit (terminals 1 and 4). (Refer to
• Under torque control, the undervoltage avoidance function (Pr.261 = "11" or "12"), which is one of the power failure time
deceleration-to-stop function, is invalid.
When Pr.261 = "11 (12)", the operation is performed in the same manner as if Pr.261 = "1 (2)".
• Under torque control, perform linear acceleration/deceleration (Pr.29 = "0 (initial value)"). When acceleration/deceleration
patterns other than the linear acceleration/deceleration are selected, the protective function of the inverter may be activated.
(Refer to
page
354.)
• Performing pre-excitation (by using the LX or X13 signal) during torque control (under Real sensorless vector control) may
rotate a motor at a low speed even though a start command (STF or STR) is not given. The inverter at a start command ON
may also rotate the motor at a low speed even though a speed limit value is set to 0. It must be confirmed that the motor running
does not cause any safety problem before performing pre-excitation.
5.4.2
Setting procedure of Real sensorless vector
control (torque control)
Sensorless
Sensorless
Sensorless
Operating procedure
1.
Perform secure wiring. (Refer to
2.
Make the motor setting (Pr.71). (Refer to
Set Pr.71 Applied motor to "0" (standard motor) or "1" (constant-torque motor).
Speed limit value
Pr.7
Speed limit
Torque control operation
operation
(Speed control)
ON
∗When the speed limit activates, torque according to the commanded is not developed.
Torque generation direction
STF signal ON
Reverse direction (forward
regenerative driving / reverse
power driving)
Forward direction (forward
power driving / reverse
regenerative driving)
page
46.)
page
5.4 Torque control under Real sensorless vector control and Vector control
Speed limit
operation
(Speed control)
ON
STR signal ON
page
235.)
505.)
Pr.8
Time
Torque
Speed limit
control
operation
operation
(Speed control)
ON
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10
267