Operation Mode Selection - Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

Pr.79
setting
Use the External/PU switchover mode (
0
(initial value)
operation mode.
At power ON, the inverter is in the External operation mode.
Operation mode
1
PU operation mode fixed
External operation mode
fixed
The operation can be
2
performed by switching
between the External and
NET operation modes.
External/PU combined
3
operation mode 1
External/PU combined
4
operation mode 2
Switchover mode
6
Switching of PU, External, and NET operation modes can be performed during operation.
External operation mode (PU operation interlock)
X12 signal ON: Switchover to PU operation mode enabled (during External operation, output
7
shutoff)
X12 signal OFF: Switchover to PU operation mode disabled
*1
The priorities of the frequency commands while Pr.79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
 Operation mode basics
• The operation mode specifies the source of the start command and the frequency command for the inverter.
• Basically, there are following operation modes.
External operation mode:
PU operation mode
:
Network operation mode
:
(NET operation mode)
Description
) to switch between the PU and External
Frequency command
Operation panel or parameter
unit
External signal input (terminal
2 and 4, JOG, multi-speed
selection, etc.)
Operation panel/parameter
unit or external signal input
(multi-speed setting, terminal
*1
4)
External signal input (terminal
2 and 4, JOG, multi-speed
selection, etc.)
For giving a start command and a frequency command with an external potentiometer or switches which are
connected to the control circuit terminal.
For giving a start command and a frequency command from the operation panel, parameter unit, or RS-485
communication via the PU connector.
For giving a start command and a frequency command via the RS-485 terminals or communication option.
Start command
or
on operation
panel or parameter unit
External signal input
(terminal STF, STR)
External signal input
(terminal STF, STR)
or
on operation
panel or parameter unit
5.9 (D) Operation command and frequency command
LED display
Refer to
: OFF
page
: ON
PU operation
mode
External operation
mode
373
NET operation
mode
PU operation
mode
374
External operation
mode
373
NET operation
mode
External/PU
374
combined
operation mode
374
PU operation
mode
375
External operation
mode
NET operation
375
mode
371
5. PARAMETERS
1
2
3
4
5
6
7
8
9
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents