Pr.190 to Pr.196 (Output terminal function
Pr.290 Monitor negative output

5.11.15 Encoder pulse dividing output

The encoder pulse signal at the motor end can be divided in division ratio set in the parameter and be output.
Use this parameter to make the response of the machine to be input slower, etc. The FR-A8AL or the FR-A8TP is required to
be installed.
Pr.
413
Encoder pulse division ratio
*1
M601
863
Control terminal option-
*2
Encoder pulse division ratio
M600
*1
This parameter is available when the FR-A8AL (option) is installed.
*2
This parameter is available when the FR-A8TP (option) is installed.
• Division waveform by division ratio
Both ON-OFF width is division times (50% duty).
• Pulse waveform example at 1000 pulse input when Pr.413 or Pr.863 = "2"
NOTE
• Control of motor rotation (forward or reverse) by phase difference between A phase and B phase is as follows.
When A phase is 90° advanced as compared to B phase: Forward rotation
When A phase is 90° behind as compared to B phase: Reverse rotation
472
5. PARAMETERS
5.11 (M) Item and output signal for monitoring
selection)page 450
selectionpage 435
Name
Initial value
1
Division ratio
A-phases
1/1
B-phases
2 divisions
Division ratio
A-phases
1/2
B-phases
Setting range
1 to 32767
Set a numerical value by which pulses are divided.
(1000 pulses)
(500 pulses)
Description