WARNING
Usage
Any person must stay away from the inverter after using the retry function as the inverter will restart suddenly after
inverter output shutoff.
It may happen depending on the inverter's function settings that the inverter does not stop its output even when the
STOP/RESET key on the operation panel is pressed. To prepare for it, provide a separate circuit and switch (to turn the
inverter power OFF, or apply a mechanical brake, etc.) for an emergency stop.
Be sure to turn OFF the start (STF/STR) signal before clearing the fault as the inverter will restart the motor suddenly
after a fault clear.
Do not use a PM motor for an application that the motor may be driven by the load and run at a speed higher than the
maximum motor speed.
Use only a three-phase induction motor or PM motor as a load on this inverter. Connection of any other electrical
equipment to the inverter output may damage the equipment.
Performing pre-excitation (by using the LX or X13 signal) during torque control (under Real sensorless vector control)
may rotate a motor at a low speed even though a start command (STF or STR) is not given. The inverter at a start
command ON may also rotate the motor at a low speed even though a speed limit value is set to zero Therefore, confirm
that the motor running does not cause any safety problem before performing pre-excitation.
Do not modify the product.
Do not remove any part which is not instructed to be removed in the Instruction Manuals. Doing so may lead to a failure
or damage of the product.
13