Mitsubishi Electric FR-A820-00046 (0.4K) Instruction Manual page 730

Fr-a800 series
Hide thumbs Also See for FR-A820-00046 (0.4K):
Table of Contents

Advertisement

 Programming example for reading the inverter status
The following program turns ON the signal Y00 of the output unit when the station 1 inverter starts running.
SB49
SW0B0.0
0
M0
X1002
3
Inverter running (RX02)
6
Remote input
One
RX3F to RX00
station
*1
These signals are assigned in the initial status. Use Pr.190 to Pr.196 and Pr.313 to Pr.315 (Output terminal function
selection) to change the output signals.
 Programming example for setting the operation mode
The following explains a program to write various data to the inverter.
The following program changes the operation mode of the station 1 inverter to network operation.
• Operation mode write code: HFB (hexadecimal)
• Network operation set data: H0000 (hexadecimal) (Refer to
• The reply code (RWr10) to the instruction code execution is set in D2. (Refer to
SB49
SW0B0.0
0
M0
X20
3
M300
7
M301
X1025
9
M302
X1025
18
24
Check the data link status of the station 1
M0
Turn ON the signal Y00 of the output unit
Y30
END
X101F
b15
b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
0
0
0
0
0
0
0
0
0
b31 b30 b29 b28 b27 b26 b25 b24 b23 b22 b21 b20 b19 b18 b17 b16
0
0
0
0
0
0
0
0
0
Inverter status
b0 : During forward rotation
b0 : During forward rotation
b2 : Running (RUN) ∗1
b3 : Up to frequency (SU) ∗1
b4 : Overload alarm (OL) ∗1
b5 : Instantaneous power failure (IPF) ∗1
b6 : Frequency detection (FU) ∗1
b7 : Fault (ABC1) ∗1
(ABC2) ∗1
b8 :
(DO0) ∗1
b16 :
(DO1) ∗1
b17 :
(DO2) ∗1
b18 :
page
Check the data link status of the station 1.
M0
PLS M300
SET M301
MOV H0FB W110
MOV H0
W111
Turn ON the instruction code execution
SET Y1025
request (RY25).
RST M301
SET M302
Read the reply code (RWr10) to D2 when the instruction
MOV W10 D2
code execution completion (RX25) turns ON.
Turn OFF the instruction code execution
RST Y1025
request (RY25).
RST M302
END
X1000
0
0
0
0
0
0
0
[Inverter status]
0
0
0
0
0
0
0
[Inverter status]
724.)
page 724
for the reply code (RWr10).)
Write the operation mode write code (HFB)
to RWw10 and the set data (H0000) to RWw11.
5.21 CC-Link IE Field Network (FR-A800-GF)
1
2
3
4
5
6
7
8
9
10
729
5. PARAMETERS

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820-00167 (2.2k)Fr-a820-00046-gf (0.4k)Fr-a820-00250 (3.7k)Fr-a820-00105-gf (1.5k)Fr-a820-00077 (0.75k)Fr-a820-00250-gf (3.7k) ... Show all

Table of Contents