2700 W Power Supply Specifications - Cisco 6503 - Catalyst Firewall Security Sys Installation Manual

Installation guide
Hide thumbs Also See for 6503 - Catalyst Firewall Security Sys:
Table of Contents

Advertisement

Appendix A
Power Supply Specifications

2700 W Power Supply Specifications

Table A-22
Table A-21
Specification
AC-input type
AC-input voltage
AC-input current
AC-input frequency
Branch circuit requirement
Power supply output
capacity
OL-5781-08
lists the specifications for the 2700 W AC-input power supply.
2700 W AC-Input Power Supply Specifications
Description
Autoranging input with power factor correction (PFC).
Note
Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
16 A maximum at 230 VAC at 2700 W output
16 A maximum at 120 VAC at 1350 W output
50/60 Hz (nominal) (±3% for full range)
Each chassis power supply should have its own dedicated, fused-branch
circuit:
For North America—20 A
For International—Circuits sized to local and national codes
All AC power supply inputs are fully isolated.
1350 W maximum (100–120 VAC)
2700 W maximum (200–240 VAC)
2700 W AC-Input and DC-Input Power Supplies
Power factor correction is a standard feature on all Catalyst 6500
series AC-input power supplies. PFC reduces the reactive
component in the source AC current allowing higher power
factors (typically 99 percent or better) and lower harmonic
current components.
Source AC can be out of phase between multiple power supplies
in the same chassis, which means that PS1 can be operating
from phase A and PS2 can be operating from phase B.
For high-line operation, the power supply operates with the hot
conductor wired to a source AC phase and the neutral conductor
wired either to ground or to another source AC phase as long as
the net input voltage is in the range of 170 to 264 VAC.
Source AC can be out of phase between AC inputs on power
supplies that are equipped with multiple AC inputs, which
means that power cord 1 can be plugged into phase A and
power cord 2 can be plugged into phase B.