Rack-Mounting The Chassis - Cisco 6503 - Catalyst Firewall Security Sys Installation Manual

Installation guide
Hide thumbs Also See for 6503 - Catalyst Firewall Security Sys:
Table of Contents

Advertisement

Chapter 3
Installing the Switch
Figure 3-4
L Brackets on the Catalyst 6504-E Switch Chassis
FA N
ST AT U
S

Rack-Mounting the Chassis

The chassis are designed to be mounted in equipment racks that meet ANSI/EIA 310-D and
Note
ETS 300-119 standards.
Two people are required to lift the chassis. To prevent injury, keep your back straight and lift with your
Warning
legs, not your back. Statement 164
We recommend that you have a third person to assist in this procedure.
Tip
To install the switch chassis into the equipment rack, follow these steps:
Determine the positioning of the chassis in the rack enclosure. Identify the rack post holes that will be
Step 1
used. If the rack post holes are prethreaded, determine if the threads are 10-32 or 12-24. If the rack post
holes are unthreaded, install either 10-32 or 12-24 clip or cage nuts over the holes to accept the
installation screws.
Note
OL-5781-08
Clip or cage nuts are not included as part of the accessory kit that comes with the chassis. You
must obtain them yourself.
Installing a Catalyst 6504-E Switch Chassis
Catalyst 6500 Series Switches Installation Guide
3-13