Red RJ45 Door terminals

The default settings
for the door outputs are, using the Red RJ45 Door Terminals:
The Door output is a Normally Open (NO) output
The Door output is powered from the panel's internal 12V power source
Internal power source for locking devices
When the power source is internal 12V, set the jumper OUT to 12V and connect the
locking device on RJ45 pins 6,7,8 (OUT) and pins 4,5 (GND).
The available voltage range is 10VDC – 12VDC. The maximum current that can be
switched is 500mA. The internal power source is shared between OUT1 and OUT
AUX1 which has a combined current of maximum 750mA. Separately this internal
power source is shared between OUT2 and OUT AUX2 which has a combined cur-
rent of maximum 750mA.
Note: The maximum current in a CAT cable is specified. Make sure the right gauge / wire
thickness is used for locking device currents
MPA2C3 Installation Guide
Move jumper to NC when Power-to-unlock device is connected
Always apply a surge device, e.g a diode in antiparallel configuration at the
locking device.
When using the MPA2S5, there is no need to add the surge device at the locking
device Only with internal power source.
87