OSDP READER ADDRESS ASSIGNMENT FEATURE VIA PANEL

Usually OSDP readers are delivered with address 0.
The reader needs to be readdressed to the appropriate address for the assigned
functions per the above table. The readdressing of the reader can be done with the
addressing tool of the reader. See instruction or installation manual of the reader
manufacturer.
The MPA2C3 panel has a built-in addressing tool for OSDP readers. Using the
below procedure you are able to connect readers one by one and program the
reader to the designated address for the dedicated function of the reader (e.g. Door
1, Reader A (IN) or Door 2 Reader B (Out)). Functions of the readers and the
respective addresses are explained in previous section. Below steps are described
for Honeywell OSDP readers from factory with default settings: Address 0 and
9600 baud communication speed.
When this menu is active, then normal operation of the panel is postponed and will
not allow normal card access control.
Prequisites for OSDP Reader addressing tool:
1. Set up the panel using Dip Switches and jumpers for OSDP1 and / or OSDP2 to
2. All readers to be connected must be set to address 0
3. Reader communication speed must be set at 9600 Baud (factory setting).
4. Only one factory reader must be connected at a time for addressing to work

Address assignment procedure for OSDP readers

Addressing readers in a new MPA2C3 panel can be done by the panel.
MPA2C3 Installation Guide
be active See "DIP Switch Settings" on page 101 and See "Jumper Settings" on
page 104