Honeywell MPA2C3 Installation Manual page 161

Access control unit
Hide thumbs Also See for MPA2C3:
Table of Contents

Advertisement

The below tables with recommendations demonstrate verified cable lengths under
the following conditions:
1. Cable used for testing CAT5E F/UTP
3. Readers tested:
4. Lock tested:
5. Panel is powered by mains power supply with 12V/7Ah battery back-up.
Note: For certified CAT 5E network a maximum cable length of 90m (295ft) is specified.
MPA2C3 Installation Guide
a. 4x2xAWG24
Other Gauges / wire diameters have not been tested.
Do not use AWG26 cables
Cable with AWG<24 may specify longer cable lengths but have not been
verified.
b. 100% Copper solid wires
CCA (Copper Cladded Aluminum) and CCS (Copper Cladded Steel) type CAT
cable will shorten the maximum length.
Tests with CCA and CCS type wires have not been performed.
a. Honeywell luminAXS 4700 (OSDP) factory default configuration
b. Honeywell luminAXS 4716 (OSDP) factory default configuration
c. HID Signo 40K (Standard) (OSDP setting) further factory default
configuration
d. Any change from factory default configuration will affect the cable length,
which has not been tested or verified.
a. 200mA lock, power-to-lock type lock (Fail safe) ; this is only a tested sugges-
tion and not a specification. Operating voltage for the lock is 10.5VDC –
13VDC.
b. Note: every type of lock has its own operating voltage range specifications,
which affects the maximum cable length.
a. The maximum length is specified with ONLY BATTERY POWERED panel.
b. Cable length specified at battery minimum voltage is 0.4V lower than the
fully charged
c. This means for a panel (in Normal Door Access Mode) with a 200mA power-
to-lock locking device and a reader:
Approx. 4 hours battery powered with 1 door / single reader
Approx. 3 hours battery powered with 2 doors / single reader
Approx. 2 hours battery powered with 4 doors / single reader.
155