Door Locking Devices / Output configurations
Connect per door the locking devices for Door OUTput / Relay (OUT) to the push in
terminal blocks or the corresponding red RJ45 Door terminal.
Each Door output (or AUX output) can be configured in 2 ways, by jumpers.
1. Output selection for locking devices powered by panel's internal power source
Current and Voltage limitations for locking power is different per power source selection.
Note:
Below tables are reflecting current and voltage limitation for 2 and 4 door system.
Table 3-10 The reflecting current and voltage limitation for 2 and 4 door system
Output Contact type
Relay contact max switching voltage and
current
(dry contact)
Max output Voltage at Door1/AUX1 output
when OUT1, AUX1 jumper onboard "12V" is
used (wet contact)
Max output current at Door1/AUX1 output
when OUT1, AUX1 jumper onboard "12V" is
used (wet contact)
80
(12V – by default) or by external
Outputs 2-door system
OUT 1-2, AUX1-2
OUT 1-2, AUX1-2 @ RJ45
OUT 1-2, AUX1-2 @ push in terminal block**
OUT 1 @ RJ45 or
OUT 1 @ push in terminal block**,
AUX 1 @ RJ45 or
AUX 1 @ push in terminal block**
OUT 1 @ RJ45 **,
AUX 1 @ RJ45 **
OUT 1 @ push in terminal block**,
AUX 1 @ push in terminal block**
power supply (Ext V – voltage fee contact).
Selectable per jumper OUT 1-2, AUX1-2:
NO (Normally Open) or NC (Normally
Closed)
500mA @ 30VDC,
500mA @ 22VAC
3A @ 30VDC,
1A @ 22VAC
10VDC ~ 14VDC
500mA per RJ45, limited to 750mA @
12VDC combined over both door output
contacts
750mA @ 12VDC combined over both door
output contacts
MPA2C3 Installation Guide