Door Monitoring Devices / Inputs
Connect per door the sensors for Door status (DrCnt) and Ergess/Request-to-EXit
(REX) to the push in terminal blocks or the corresponding red RJ45 Door terminal.
Push in Terminal Block
The default settings for the door inputs are, using the push in terminal blocks :
The REX input is a Normally Open (NO) input, without end-of-line (EOL) resistors.
DrCnt input is a supervised, Normally Closed (NC) input, set for 2.2 kOhm EOL
resistors.
76
OUT4 , COM4 /
Return4
You can connect the NO contacts of the REX switch or sensor immediately to the
REX and GND input of the panel.
You can connect the NC contacts of the Door monitoring switch or sensor with
two 2.2 kOhm to the DrCnt and GND input of the panel. See picture per below.
(COM) PIN 3
(OUT) PIN 6,7,8
Door Lock
(GND) PIN 4,5
MPA2C3 Installation Guide