Honeywell MPA2C3 Installation Manual page 104

Access control unit
Hide thumbs Also See for MPA2C3:
Table of Contents

Advertisement

The interface bus is wired to the access panel by using standard CAT 6E/7 (S)/
FTP/UTP cable with RJ45 plug (J16) on the panel. The interface bus has a fixed
baud rate and communicates to the downstream I/O devices using a polling tech-
nique.
Each downstream I/O device needs to have a unique address for proper communi-
cation. Each one also has some configuration jumpers that need to be positioned
correctly. The following table lists the DIP switch and jumper settings for the NX4IN
and NX4OUT downstream devices.
Table 3-11 Downstream I/O Devices DIP Switch and Jumper Settings
Module
NX4IN
NX4OUT
98
Setting
DIP switches
Jumper settings
DIP switches
Value
Address (switches 1-6) – 1 or 2
Baud rate (switches 7 and 8) – 7 = OFF,
8 = ON
OP Mode (switches 9 and 10) – 9 =
OFF, 10 = OFF
JP1 – ON, positions 1 and 2 (if the
module is the last module on the
downstream bus),
OFF positions 2 and 3 (if the module is
not the last module on the
downstream bus)
JP2 – any setting
JP3 – any setting
JP4 – NORMAL
(Positions 1 and 2)
Address (switches 1-6) – 3 through 6
MPA2C3 Installation Guide