FACP input prerequisites

The MPA2C3 has a dedicated fully hardware controlled FACP (Fire Alarm Control
Panel) input. When triggered the panel overrides immediately and simultaneously
the 4 door outputs (OUT1, OUT3 (AUX1), OUT2, OUT4 (AUX2)) to a Fail-safe state
(door unlocked state*). AUX REL 5,6,7 and 8 are NOT affected hardware wise by
the FACP input. See the installation manual for FACP installation.
Note: Individual doors cannot be selected to be fail-safe or fail-secure. All door outputs are
affected.
When the FACP input is activated:
All door outputs (OUT1, OUT3 (AUX1), OUT2, OUT4 (AUX2)) are in safe condition
(safe = off = unlocked door* = free egress).
None of the door outputs (OUT1, OUT3 (AUX1), OUT2, OUT4 (AUX2)) can be con-
trolled by card readers, egress buttons or access control software.
There is a notification in the Web UI that the FACP input has been activated. Host
software will be notified.
To achieve the above functionality the panel needs to be set to the Reversed Door
Access Mode. In Reversed Door Access Mode the Door Outputs (OUT1, OUT3
(AUX1), OUT2, OUT4 (AUX2)) are reversed.
In Reversed Door Access Mode all Door Relays (OUT1, OUT3 (AUX1), OUT2, OUT4
(AUX2)) are energized when the doors are supposed to be locked. To unlock a door
the Door relay must be in de-energized state.
Always test the full end to end functionality of the FACP input and the effect to the
doors (not only the outputs) after the installation has been completed.
FACP input not activated: Doors 1 to 2/4 function as access-controlled doors,
using cards, egress or software/Web User Interface.
MPA2C3 Installation Guide