Installation Instructions / ACS-8
6.
ACS-8/cables
6.1
ACS-8 supply voltage
Please observe the informations about grounding and shielding in chapter 5.
6.1.1 ACS-8 230 V version
Parameter
operating voltage range
mains frequency
power supply cable type
6.1.2 ACS-8 12V version
Parameter
operating voltage range
current consumption
The door strike must be taken into consideration if its supply comes from the ACS-8. The current
consumption of a door strike depends on the type, but lies somewhere between 200mA and 500mA.
The current consumption of an energized door strike must be known for each ACS-8 when
designing a 12 V system.
The following drawing (powered on) shows the voltage drop of a 1.5mm
A power consumption of 1A is calculated for each ACS-8.
Observe the outgoing and return line.
Value
230 V AC –15% +10%
40 – 60 Hz
NYM 3 x 1,5 mm²
Value
10.0V to 15.0V DC
depends on the reader type, the number of readers and the interface type
cable compared to a 4mm
2
17
cable.
2