The current value is marked with "=>". To modify the values enter "y" and confirm with Enter. Then
you can select one of the consecutive numbers.
Settings and their use:
The following information can be checked and edited depending on the selected protocol:
Baud rate:
Address:
Group address:
Example:
1.
9-bit-ZK/ZE Prot.
2.
=>DIN prot.
3.
RDT prot.
4.
Event prot.
Status: Addr: 32; GAddr: 30; 19200 bauds
Change? Y/N:_
9-bit-ZK/ZE prot.:
DIN prot.:
RDT prot.:
Event prot.:
The current value is marked with "=>". The value can be modified by
entering "y" and Enter (when the question Change? Y/N appears) and the
required baud rate number (the factory setting is 19200).
The current address and the permitted address range are displayed. The
address can be modified by entering "y" + Enter (when the question
Change? Y/N appears) and the desired address (the factory setting is 32).
The current group address and the permitted address range are displayed.
The address can be modified by entering "y" + Enter (when the question
Change? Y/N appears) and the desired address (the factory setting is 30).
Difference between address and group address:
The system can support up to 30 groups of 32 controllers (960 in all).
Address refers to the identifying number of any controller in a group (1 - 32).
Group address refers to the identifying number for each group (1 - 30)
(MultiAccess for Windows / IQ MultiAccess can currently manage a maximum of
512 controllers)). Combining the Group address and the address uniquely
identifies every controller in the system.
Example:
-----
Direct connection to RS232 (e.g. PC/notebook) or interface
converter
For modem operation
For network operation using an Ethernet interface
Group
addresses
address
1
1 - 32
2
1 - 32
3
1 - 32
4
1 - 32
etc.
30
1 - 32
Installation Instructions / ACS-8