Module supply:
Total current consumption of the modules:
Calculation of the maximum line resistance:
Calculation of the maximum possible line length:
Power supply door strike:
Current consumption: 230mA
Calculation of the maximum line resistance:
Calculation of the required cross-section:
Calculation of the number of wires with a wire cross-section of 0.6mm (Ø 0.28mm²):
contactless / proximity reader (026390.10)
4I/2O-module (026592)
display module (027555)
keypad module (027570)
total:
R
=
Uv
L
I
i
=
electrical conductivity
L
= A x R
x i
L
2
R
=
Uv
L
I
i
=
electrical conductivity
A
=
2 x L
R
x i
L
no. of wires
=
=
500mV =
570mA
=
=
0.877 x 56m
Ωmm²
2
=
500mV =
230mA
=
=
2 x 24.556m
2.17 Ω * 56m
Ωmm²
0.40mm²
=
0.28mm²
Installation Instructions / ACS-8
140mA
230mA
150mA
50mA
570mA
0.877Ω
56m
of copper
Ωmm²
=
24.556m
2.17Ω
56m
of copper
Ωmm²
=
0.40mm²
1.42 wires ! 2 wires