Power supply door strike:
Current consumption:
Calculation of the maximum line resistance:
Calculation of the required cross-section:
Calculation of the number of wires with a wire cross-section of 0.28mm² (diameter 0.6mm):
Calculation of the number of wires with a wire cross-section of 0.5mm² (diameter 0.8mm):
Result:
Line cross-section for module supply:
Line cross-section for the supply of the door strike:
J-Y(St)Y 5x2x0.6Ø or 4x2x0.8Ø can be used as the power supply for the module electronics and the bus
line, providing the the cable length does not exceed 40m.
A separate line with a minimum line cross-section of 0.66mm² must be used to power the door strike.
230mA
R
=
Uv
L
I
i
=
electrical conductivity
A
= 2 x L
R
x i
L
no. of wires
=
no. of wires
=
=
500mV =
230mA
=
=
2 x 40m
2.17Ω * 56m
Ωmm²
0.66mm²
=
0.28mm²
0.66mm²
=
0.5mm²
0.855mm²
0.66mm²
Installation Instructions / ACS-8
2.17Ω
56m
of copper
Ωmm²
=
0.66mm²
2.25 wires ! 3 wires
1.32 wires ! 2 wires