Installation Instructions / ACS-8
Insert/change lithium battery
9.5
Danger!
The device contains a lithium battery.
To avoid the risk of fire or burns, the battery must not be damaged, short-circuited or reloaded.
Do not contact it with fire or water. There is a risk of explosion if the battery is changed
improperly.
Replace the battery only by the same or an equivalent type recommended by the manufacturer.
Dispose used batteries according to EU guidline 2006/66 (see info next page).
A batteriy change must only be carried out by qualified personell introduced to the VDE
regulations.
Danger of data loss / disruption in operation!
All data will be lost if the device is set to dead-voltage and the battery is removed. Data must be
reloaded to the controller via the AC-software function "Load data". According to the amount
of data, this procedure may vary in length of time. During this time the concerned doors are
without any function.
If the power fails, the data is maintained by a lithium battery.
The life span of the lithium battery is approx. 3 years. If a power failure occurs for a lengthy period, the capacity
of the battery is considerably reduced.
Since the status of the battery cannot be clearly determined it is recommended that the battery be changed
every two years.
Lithium battery (type CR 2477N, 3 V 950 mAh) for data preservation in ACS-8 = item no. 018050.
"Battery empty" Message
The ACS-8 continuously checks the status of the lithium battery. If the voltage reaches a critical state,
MultiAccess for Windows or IQ MultiAccess issues the "Battery empty" message and the "Tamper" LED of the
ACS-8 lights up.
In this instance, the battery must be replaced immediately.
Procedure
1.
Open the device as described in
chapter 8.2 ,steps 1 to 4.
Bear in mind that the tamper switch
is activated; you have to reset the
tamper message of the respective
controller in MultiAccess for
Windows or IQ Multi Access.
Example in MultiAccess for Win-
dows with ACS-2plus (ACS-8 is
identical):
- System data
- System parameter
- Terminal
- Alarm/display reset