Mau Connection; Controlnet Network; Figure 3-2 Lcn Mau To Lcn Cable T-Connections - Honeywell PE SC1430 Planning, Installation And Service Manual

Table of Contents

Advertisement

3. Operation
3.2. Network Connections

MAU connection

Connect the MAU to both Cable A and Cable B coax T-connector as shown below
(tower unit MAU shown, cabinet mounted MAU similar).

Figure 3-2 LCN MAU to LCN Cable T-Connections

ControlNet Network

A ControlNet network is a single coaxial trunk cable broken up into segments
interconnected by links. Node connections to the network are created through a tap and
drop cable. Repeaters are used to link segments together and for changes in media from
coax to fiber optic. All points on the network must either have an interface card or a
terminator. Terminators are comprised of termination resistors, which are used to mark
the beginning and end of a trunk segment and TDLs (Tap dummy load) which terminate
a drop cable when no node is present. The model number for the Universal ControlNet
Interface is TC-PCIC02-100.
46
PE SC1430-Based Honeywell Server PE SC1430-Based Honeywell Server
Honeywell
12/2007